APCUPSD(8) | System Manager's Manual | APCUPSD(8) |
apcupsd
— a daemon
for controlling most APC UPSes
apcupsd |
[-b ] [-d
level | --debug
level] [-f
file | --config-file
file] [-P
file | --pid-file
file] [-p |
--kill-on-powerfail | -t |
--term-on-powerfail ]
[-R ] |
apcupsd |
[-k | --killpower |
--hibernate | -o |
--power-off ] |
apcupsd |
[-h | --help ] |
apcupsd |
[-V | --version ] |
The apcupsd
daemon controls the operation
of most American Power Conversion Corp (APC) UPSes. During a power failure,
apcupsd
informs users about the loss of utility
power and that a shutdown may occur. If utility power is not restored, a
system shutdown will follow when the battery is exhausted, a specified
timeout expires, a specified battery charge percentage is reached, or a
specified battery runtime (based on internal UPS calculations and determined
by power consumption rates) expires. If the utility power is restored before
one of the these shutdown conditions is met, apcupsd
will inform users of this and the shutdown will generally be cancelled.
Refer to the Implementation Notes section below for situations in which the
shutdown may not be cancelled.
The meaning of the command line options is as follows:
-b
-d
level --debug
level-f
file --config-file
fileapcupsd
on the same
computer to control multiple UPSes.-k
|
--killpower
|
--hibernate
apcupsd
itself to power
down the UPS after a system shutdown has almost completed. In hibernate
mode, the UPS will again supply power to the system when the utility power
returns.-o
|
--power-off
-P
file --pid-file
fileapcupsd
on the same
computer to control multiple UPSes.-p
--kill-on-powerfail
apcupsd
commands the UPS to power down in
hibernate mode just before apcupsd
starts the
system shutdown. This relies on the grace shutdown delay of a Smart-UPS
being long enough to allow the system to shutdown completely before the
UPS shuts off the power to the system and goes into hibernate mode. This
shutdown grace delay is a programmable value stored in a Smart-UPS EEPROM
which can be changed using apctest(8). In hibernate
mode, the UPS will again supply power to the system when the utility power
returns. Refer to apcupsd.conf(5) for an alternative
method using the KILLDELAY configuration directive and the only method
available when using a Back-UPS or other UPS operating in simple
signalling mode.-t
--term-on-powerfail
apcupsd
exits immediately when it issues the
system shutdown command. This behaviour is useful for those systems where
it is not possible to insert apcupsd
commands in a
halt script to issue the killpower command. Without this option,
apcupsd
will wait for the SIGTERM signal from the
system shutdown process before exiting.-R
-v
--version
apcupsd
version number and the program
help.-h
--help
The apcupsd
daemon supports a networking
mode called Network Information Server (NIS) -- not related to Sun's NIS/YP
-- in which the daemon serves status and event information to clients over a
network. See the "Running The Network Information Server" section
of the apcupsd manual for more information and configuration details on this
mode.
The apcupsd
daemon also supports a
Smart-UPS in SNMP mode provided an APC Web/SNMP or APC PowerNet SNMP card is
installed in the UPS's SmartSlot. For more information and configuration
details on this mode, refer to the "Support for SNMP UPSes"
section of the apcupsd manual.
The shutdown is made by calls to the script
/etc/apcupsd/apccontrol by the
apcupsd
daemon. Consequently, no changes to
/etc/inittab are necessary on Linux as there is no
communication between the daemon and the init(1) process. Installation of
the daemon modifies the halt script so that at the end of the shutdown
process, the daemon will be re-executed to power off the UPS in hibernate
mode.
On some operating systems (eg FreeBSD) there is no halt script so
apccontrol must be modified to cause the daemon to power off the UPS after a
delay. Alternatives are to use the --kill-on-powerfail command on the
apcupsd
command line or refer to
apcupsd.conf(5) for details of the KILLDELAY configuration
directive.
It will almost certainly be necessary to customise the configuration information in the /etc/apcupsd/apcupsd.conf configuration file to suit your configuration and desired UPS behaviour.
For information on the configuration directives and the format of the configuration file, refer to apcupsd.conf(5).
apcupsd
generates events when certain
conditions occur. These events are sent to the system log and, optionally,
to the temporary events file
(/var/log/apcupsd.events). They also generate a call
to the /etc/apcupsd/apccontrol script which in turn
will call any custom scripts placed in the
/etc/apcupsd directory which may override
apccontrol's default behaviour. For details of the events and customising
apccontrol's behaviour, refer to apccontrol(8).
If the DATATIME configuration directive is set to non-zero,
apcupsd
will log a data record at the interval
defined by the DATATIME directive. This data record is in a format similar
to the APC PowerChute software data file format.
The status report output format is simple ASCII. Generally there is a single piece of information on each line of output. The content varies based on the model of UPS being used and, in some cases, the firmware version. This status report is also optionally written the the /etc/apcupsd/apcupsd.status file. Refer to apcaccess(8) for full details of the status report output.
/etc/apcupsd/apcupsd.conf default configuration file
/var/run/apcupsd.pid default process ID file
/var/log/apcupsd.status optional status file
/var/log/apcupsd.events default events file
apcupsd.conf(5), apcaccess(8), apccontrol(8), apctest(8).
The HTML apcupsd manual installed on your system or available online at http://www.apcupsd.org/
Trevor Roydhouse (current)
Andre M. Hedrick
Christopher J. Reimer
Adam Kropelin (current Project Manager and Code
Maintainer)
Kern Sibbald (former Project Manager and Code
Maintainer)
Riccardo Facchetti (former Project Manager and Code
Maintainer)
Andre M. Hedrick (Project Founder and former Code
Maintainer)
An enormous number of users who have devoted their time and energy to this project -- thanks.
January 10, 2009 | apcupsd v3.14.6 |